 |
A. Manometer Method
(Low Pressure Testing Procedure)
In this method a low pressure test gauge
(ECII 2434A) or a Water manometer ( 1212Kit
) is used to detect pressure loss due to
leaks.
Step 1. Inspect all connections and appliance
valves to be sure such connections are wrench
tight and that all appliance connections
are closed including pilot valves and all
line shutoff valves.
Step 2. Connect low pressure test gauge or
manometer to a range top burner orifice.
If a range is not available a special tee
may be installed between the appliance shut-off
and inlet to the appliance. Several shut
off valves have a pressure tap port that
may be used.
Step 3. Open container valve to pressure piping
system. Leave it open for two or three seconds
then close tightly. Return to appliances
and open each appliance piping shut-off valve
slowly. If the pressure drops below 10 inches
water column repeat step 3.
Step 4. Observe indicated pressure on low
pressure test set or manometer. This reading
should be at least 11 inches water column.
Now slowly open one burner valve on an appliance
or bleed through a pilot valve enough gas
to reduce pressure reading on the test set
or water manometer to exactly 9 inches water
column.
A 10 minute constant pressure
indicates a
leak tight system. A drop in
pressure indicates
a leak in the system. If a drop
occurs, check
joints and other possible points
of leakage
with an approved combustible
gas detector,
Liquid Leak Detector, soap and
water, or
an equivalent non-flammable solution.
CAUTION:
Since some leak test solutions,
including
soap and water, may cause corrosion
or stress
cracking, the piping should be
rinsed with
water after testing, unless its
determined
the leak test solution is non-corrosive.
Never
test with an open flame. If there
is an increase
in pressure it indicates the
container valve
is not shut off completely. Shut
off container
valve tightly and repeat step
4. It is wise
to install a redundant shut-off
valve at
the tank valve outlet to ensure
that there
is no seepage through the container
valve's
stem seat and valve body.
B. Gauge Adapter Method (High Pressure Testing
Procedure)
Step I . Inspect all connections and appliance
valves to be sure such connections are wrench
tight and that all appliance valves are closed
including the pilot valves.
Step 2. Install a ECII (Rego) 2962 high pressure
test gauge adapter on the tank service valve
and connect the other end of the gauge adapter
to the pigtail and regulator inlet.
Step 3. Open container valve to allow the
system to pressurize while observing indicated
pressure on 300 pound testing gauge.
Step 4. Close service valve tightly. Note
pressure reading on the pressure gauge, then
slowly bleed gas between service valve and
gauge adapter, reduce pressure by 10 pounds
per square inch and retighten gauge adapter
into service valve, note reading on gauge.
If gauge reading remains constant for 10
minutes it can be assumed the system is leak
tight. If the pressure reading drops, It
indicates a leak somewhere in the high or
low pressure piping system. NOTE: A pressure
drop of 15 psig in 10 minutes time, indicates
a leak as little as 10 BTU of gas per hour.
Check joints and other possible points of
leakage with an approved combustible gas
detector, liquid leak detector, soap and
water, or an equivalent non-flammable solution.
CAUTION: Since some leak test solutions, including
soap and water, may cause corrosion or stress
cracking, the piping should be rinsed with
water after testing, unless its determined
the leak test solution is non-corrosive. Never
test with an open flame. If there is an increase
in pressure it indicates the container valve
is not shut off completely. Shut off container
valve tightly and repeat step 4.
Step 5. Disconnect the 2962 test gauge adapter
from the service shut off valve. Reconnect
pigtail, tighten and test with soap and water
or an appropriate leak detector solution,
(refer to caution in 4. above). Step 6. Proceed
with manometer method, steps 2 through 4.
Never check for leaks with an open flame.
NOTE: After the piping system
and appliance
connections have been proven
to be leak tight,
the air may be purged from lines
. Refer
to NPGA safety handbook section
403 and NFPA
54 for more information, or the
B149 Installation
Code.
Regulator Delivery Pressure
Check the regulator delivery pressure with
approximately half the total appliance load
in use. Your gauge should read 11 inches
water column (or 6 1/3 ounces per square
inch) at the appliance. Adjust regulator
if necessary, following this, turn on all
appliances to make sure that pressure is
maintained at full load. If an excessive
pressure drop occurs, inspect line for "kinks",
"flats" or other restrictions.
CAUTION: Appliance regulators are installed on most
appliances and may be preset
by the manufacturer
for flow pressure lower than
11 inches water
column, it is recommended the
manometer or
test gauge be installed at a
location other
than the range orifice or appliance
pressure
tap when performing lock-up and
delivery
pressure checks.
Regulator Lock-up and Leakage
After this, shut off all appliance valves
to determine if the regulator has a worn
seat or if it has been set too high to compensate
for line losses due to undersized piping.
A slight rise in pressure will occur under
these conditions. This is called the "lock-up"
pressure. The lock-up pressure should not
exceed 120% of the set delivery pressure
for the given tank pressure. A quick rise
in pressure above this point will indicate
undersized piping.
Continue this same test for 5 minutes or
more. If a creeping rise is noticed in the
pressure, the regulator seat is not closing
off properly. Inspect regulator inlet nozzle
for dirt, scratches or dents and seat disc
for signs of wear. Replace where necessary.
For more information, refer to
NFPA 54, Section
on Inspection, Testing and Purging,
NPGA
Safety Bulletin 403 pressure
testing and
leak checking LP Gas piping system.
For more
information on setting single
stage regulators,
request Rego Products Technical
Guide 107.
Leak Testing an Existing System Being Placed
Back in Service
According to NFPA 54, Appendix
D (1992 Edition),
leak checks on systems being
placed back
in service should include all
regulators,
including appliance regulators
and control
valves in the system. All shut-off
valves
found before the appliances should
be turned
on for the leak check as well
as the appliance
control valve that utilizes 100
% pilot shut-off
valves. This test will help prove
the integrity
of the 100 % pilot shut-off valve
for each
appliance.
If there are appliances that
are not equipped
with a 100% pilot shut-off system,
the manual
gas valve should be placed in
the off position
prior to leak testing.
A. Manometer Method
Step I . Insert a water manometer or equivalent
device (ECII -Rego 1212Kit or 2434A) into
the system downstream of the final stage
regulator.
Step 2. Pressurize the system with LP-Gas
or Air to a test pressure of 11 " water
column. This can be accomplished by opening
the container valve for two or three seconds
then closing tightly. If the pressure reading
on the test device is below 10" w.c.,
repeat this step.
Step 3. Observe the pressure indicated on
low pressure test device, it should read
at least 11" w.c.. Release enough pressure
through an appliance burner valve or other
suitable means to drop the system pressure
to 9" w.c.. There should be no loss
or gain in pressure for a period of 3 minutes.
If leakage is indicated by a drop in pressure,
check all equipment or outlets for leaks.
If they are leak-free, check all joints and
other possible points for leakage with an
approved combustible gas detector, soap and
water, liquid leak detector or an equivalent
non-flammable solution. If there is an increase
in pressure, it indicates the container valve
is not shut off completely. Shut off container
valve tightly and repeat Step 3.
CAUTION: Since some leak test solutions, including
soap and water may cause corrosion
or stress
cracking, the piping should be
rinsed with
water after testing, unless its
determined
the leak test solution is non-corrosive.
Never
test with an open flame.
B. Gauge Adapter Method
Step 1. Insert an ECII Rego 2962 high pressure
test gauge adapter between the container
gas shut-off valve and the inlet of the first
stage regulator in the system.
Step 2. Open container valve while observing
indicated pressure on the 300 pound testing
gauge. Allow the system to pressurize and
close the container shut-off valve.
Step 3. Slowly bleed enough gas from the
system to lower Pressure reading by 10 psig.
Note reading on gauge. Allow this test to
stand for 3 minutes without showing an increase
or decrease in pressure.
If leakage is indicated by a drop in pressure,
check all equipment or outlets for leaks.
If they are leak-free, check all joints and
other possible points for leakage with an
approved combustible gas detector, soap and
water, or an equivalent non-flammable solution.
If there is an increase in pressure, it indicates
the container valve is not shut off completely.
Shut off container valve tightly and repeat
Step 3.
CAUTION: Since some leak test solutions, including
soap and water, may cause corrosion or stress
cracking, the piping should be rinsed with
water after testing, unless its determined
the leak test solution is non-corrosive. Never
test with an open flame.
|
 |